The defaulted setting for T-506 temperature controller of S&A Teyu industrial water chiller is intelligent temperature control mode. If you want to set the water temperature to 20℃, you need to switch to constant temperature control mode first and then set the required water temperature. Detailed steps are as follows:
Adjust T-506 from intelligent mode to constant temperature mode.
1.Press and hold “▲”button and “SET” button for 5 seconds
2.until the upper window indicates “00” and the lower window indicates “PAS”
3.Press “▲” button to select the password “08” (default setting is 08)
4.Then press “SET” button to enter menu setting
5.Press “▶” button until the lower window indicates “F3”. (F3 stands for way of control)
6.Press “▼” button to modify the data from “1” to “0”. (“1” means intelligent mode while “0” means constant temperature mode)
Now the chiller is in constant temperature control mode.
Adjust water temperature.
Method One:
1.Press “SET” button to enter “F0” interface.
2.Press “▲” button or “▼” button to adjust water temperature.
3.Press “RST” to save the modification and exit the setting.
Method Two:
1.Press and hold “▲” button and “SET” button for 5 seconds
2.Until the upper window indicates “00” and the lower window indicates “PAS”
3.Press “▲” button to select the password (default setting is 08)
4.Press “SET” button to enter menu setting
5. Press “▲” button or “▼” button to adjust water temperature
6. Press “RST” to save the modification and exit the setting