Heater
Filter
US standard plug / EN standard plug
Small industrial chiller CWUP-10 is designed specifically for ultrafast laser and UV laser. Small as it is, its temperature control ability doesn’t compromise. This laser water chiller delivers superior temperature control of ±0.1°C with PID control technology. It is designed with a compressor refrigeration circuit with properly designed pipeline arrangement, which avoids the generation of bubble to reduce the impact to the lasers. What makes CWUP-10 industrial chiller even unique is that it incorporates the RS485 communication function, providing higher level of communication between the chiller and the laser system.
Model: CWUP-10
Machine Size: 58X29X52cm (L X W X H)
Warranty: 2 years
Standard: CE, REACH and RoHS
Model | CWUP-10 | |
CWUP-10AI | CWUP-10BI | |
Voltage | AC 1P 220-240V | AC 1P 220~240V |
Frequency | 50Hz | 60Hz |
Current | 0.6~5.3A | 0.6~5.3A |
Max. power consumption | 1.04kW | 1.04kW |
| 0.39kW | 0.39kW |
0.52HP | 0.53HP | |
| 2559Btu/h | |
0.75kW | ||
644Kcal/h | ||
Refrigerant | R-134a | |
Precision | ±0.1℃ | |
Reducer | Capillary | |
Pump power | 0.09kW | |
Tank capacity | 6L | |
Inlet and outlet | Rp1/2” | |
Max. pump pressure | 2.5bar | |
Max. pump flow | 15L/min | |
N.W. | 24Kg | |
G.W. | 27Kg | |
Dimension | 58X29X52cm (L X W X H) | |
Package dimension | 65X36X56cm (L X W X H) |
The working current can be different under different working conditions. The above information is for reference only. Please subject to the actual delivered product.
Intelligent functions
* Low tank water level detecting
* Low water flow rate detecting
* Over water temperature detecting
* Heating of the coolant water at low ambient temperature
Self-check display
* 12 types of alarm codes
Easy routine maintenance
* Toolless maintenance of dustproof filter screen
* Quick-replaceable optional water filter
Communication function
* Equipped with RS485 Modbus RTU protocol
Heater
Filter
US standard plug / EN standard plug
Digital temperature controller
The T-801B temperature controller offers high precision temperature control of ±0.1°C.
Easy-to-read water level indicator
The water level indicator has 3 color areas - yellow, green and red.
Yellow area - high water level.
Green area - normal water level.
Red area - low water level.
Modbus RS485 communication port
We're here for you when you need us.